To calibrate a Magnehelic pressure gauge, the process involves verifying and adjusting the device's accuracy by comparing it with a reference standard or pressure source. Here's a general procedure for calibrating the Magnehelic pressure gauge:
Preparation
Ensure Equipment is Clean and Functional: Make sure the Magnehelic gauge and the calibration equipment are in good working condition.
Select a Reference Pressure Source: Use a precise, known pressure source or a micro-pressure pump capable of generating low pressures with high accuracy (such as a calibration pump or deadweight tester).
Ensure Proper Setup: The calibration system should be in a stable environment (free from temperature or humidity fluctuations) to minimize errors.
Zero the Magnehelic Gauge
Set to Zero: Before calibration, ensure that the Magnehelic gauge is at zero pressure. If needed, adjust the gauge's zeroing screw or knob to bring the needle to zero.
Apply Known Pressures
Apply Calibration Pressures: Use your reference pressure source (such as a precision micro-pressure pump) to apply known, accurate pressures at various points. Typically, you would apply at least 3 to 5 different pressure points across the range of the Magnehelic gauge (e.g., 10%, 50%, and 100% of the full-scale pressure).
Record the Readings: For each applied pressure point, compare the reading on the Magnehelic gauge to the known pressure from the reference source.
Compare the Readings
Identify Differences: If the reading on the Magnehelic gauge is off from the reference pressure, note the difference at each calibration point.
Adjust the Magnehelic Gauge
Make Adjustments: If necessary, adjust the Magnehelic gauge's internal calibration screw or mechanism (depending on the model) to match the known pressure. Follow the manufacturer's instructions for how to make this adjustment.
Repeat Testing: After making adjustments, re-test the Magnehelic gauge at the same pressure points to ensure the readings are now accurate.
Final Check
Verify Accuracy: Perform a final test across the full range to ensure the gauge is accurate at all pressure levels.
Document Calibration: Record the calibration results, noting any adjustments made and the final readings. Calibration certificates may be required for ISO or other compliance standards.
Environment Control: Temperature and humidity can affect pressure readings, so it's important to calibrate in a controlled environment.
Pressure Source Accuracy: Always use a highly accurate reference pressure source to avoid discrepancies during calibration.
Regular Calibration: Periodically calibrate the Magnehelic gauge (according to the manufacturer's recommended schedule) to maintain its accuracy over time.