Temperature transmitters play a crucial role in industrial automation, process control, and laboratory research, converting temperature sensor signals into standardized electrical outputs. Over time, transmitters can drift, requiring regular calibration to maintain accuracy.
The PR611 Series Multifunctional Dry Block Calibrator provides a precise and automated method for calibrating temperature transmitters, featuring built-in electrical measurement channels, HART communication support, and fully customizable calibration tasks.
This article provides a detailed step-by-step guide to calibrating transmitters using the PR611 calibrator.
Temperature transmitters convert sensor signals (from thermocouples or RTDs) into standardized electrical outputs (4-20mA, 0-10V, etc.). However, they can develop errors due to:
Component aging and wear.
Electrical interference in the system.
Temperature fluctuations affecting internal components.
Regular calibration ensures:
✔ Accurate temperature transmission
✔ Process control stability
✔ Compliance with ISO and industry standards
✔ Supports both current (mA) and voltage (V) transmitters.
✔ Built-in HART communication (PR611H/PR613H models) for smart transmitters.
✔ Dual-zone temperature control for stable calibration conditions.
✔ Automated test cycles reduce manual workload.
✔ PR611 Multifunctional Dry Block Calibrator
✔ Temperature transmitter to be calibrated
✔ Power supply (if not powered by PR611’s 24V loop)
✔ Wiring connectors and test cables
✔ HART communicator (if needed for smart transmitters)
✔ USB drive (for data logging, if required)
PR611 supports the calibration of:
Current-output transmitters (4-20mA)
Voltage-output transmitters (0-10V, 1-5V, etc.)
HART-enabled smart transmitters
Check the manufacturer’s specifications for expected input/output values.
For 4-20mA transmitters, follow these steps:
Connect the positive (output) wire to the 50mA terminal on PR611.
Connect the negative (ground) wire to the COM terminal.
If needed, enable 24V loop power from PR611.
For 0-10V transmitters, follow these steps:
Connect the positive (output) wire to the 50V terminal.
Connect the negative (ground) wire to the COM terminal.
For HART-enabled transmitters, follow these steps:
Connect the transmitter wiring as per the 4-20mA setup.
Ensure PR611’s built-in 250Ω resistor is enabled.
Open the HART communication module on PR611 to interact with the transmitter.
Power on PR611 and navigate to the Calibration Interface.
Select Transmitter Calibration Mode.
Choose the correct electrical measurement type:
50mA for current-output transmitters
50V for voltage-output transmitters
In Task Settings, define:
Minimum and maximum temperature range (e.g., 0°C to 100°C).
Expected electrical output values (e.g., 4mA at 0°C, 20mA at 100°C).
Enable automatic stabilization detection to ensure accurate readings.
If calibrating a HART transmitter, switch PR611 to HART mode.
Connect to the transmitter and read its current calibration settings.
Modify settings if needed (e.g., zero and span adjustments).
Set PR611’s temperature setpoint to the first calibration point (e.g., 0°C).
Wait for temperature stabilization.
Record the transmitter’s electrical output (mA or V).
Repeat steps 1-3 for multiple calibration points (e.g., 50°C, 100°C).
Compare the measured output values with the expected results. Common errors include:
Zero shift (4mA output is too high or too low).
Span error (20mA output is incorrect at max temperature).
Non-linearity (uneven response between calibration points).
Use the HART communicator or transmitter settings to adjust:
Zero point (aligns 4mA output with 0°C).
Span point (aligns 20mA output with the max temperature).
Re-run the calibration to confirm accurate output alignment.
✔ Save data to PR611’s internal memory or export via USB.
✔ Generate a calibration certificate for compliance.
✔ Use PR611’s stabilization detection to improve accuracy.
✔ Calibrate at multiple points to verify transmitter linearity.
✔ Enable 24V loop power if the transmitter doesn’t have an external power supply.
✔ Perform regular calibrations to prevent drift over time.
✔ Use HART communication for advanced diagnostics and settings adjustments.
✔ Temperature stability of ±0.01°C, ensuring accurate sensor calibration.
✔ Measures 4-20mA current and 0-10V voltage outputs.
✔ Built-in 250Ω resistor for HART communication.
✔ Heats from 23°C to 155°C in 17 minutes.
✔ Cools from 23°C to -30°C in 12 minutes.
✔ Saves calibration data for compliance and documentation.
The PR611 Multifunctional Dry Block Calibrator is an ideal tool for transmitter calibration, providing high-precision temperature control, electrical measurement, and HART communication capabilities. Whether used in industrial automation, research labs, or process control applications, PR611 ensures accurate, efficient, and repeatable transmitter calibration.
By following the step-by-step calibration process outlined above, users can ensure reliable transmitter performance while maintaining compliance with industry standards.